LV432808; Schneider Electric -Circuit Breaker
range |
Compact
|
|
---|---|---|
range of product |
NSX400...630
|
|
product or component type |
Basic frame
|
|
device short name |
Compact NSX630N
|
|
device application |
Distribution
|
|
circuit breaker name |
Compact NSX630N
|
|
poles description |
4P
|
|
neutral position |
Left
|
|
network type |
AC
|
|
network frequency |
50/60 Hz
|
|
[In] rated current |
630 A ( 40 °C )
|
|
[Ui] rated insulation voltage |
800 V AC 50/60 Hz conforming to IEC 60947-2
|
|
[Uimp] rated impulse withstand voltage |
8 kV conforming to IEC 60947-2
|
|
[Ue] rated operational voltage |
AC 50/60 Hz conforming to IEC 60947-2
|
|
breaking capacity code |
N
|
|
breaking capacity |
10 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
22 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2 85 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 30 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2 42 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 20 kA at 600 V AC 50/60 Hz conforming to UL 508 50 kA at 480 V AC 50/60 Hz conforming to UL 508 85 kA at 240 V AC 50/60 Hz conforming to UL 508 |